• Input
    Voltage:
    120VAC or 24VAC
    Frequency:
    50/60 Hz
    Tolerance (voltage):
    ± 15% of nominal
    Power Consumption:
    10 VA maximum
    Transient Protection:
    Isolation transformer (120 VAC only)
  • Output
    Type:
    Electromechanical relay
    Rating:
    10A - 1/6HP at 120VAC, 1/3HP at 24VAC
    Mechanical Life:
    10,000,000 operations
    Electrical Life:
    300,000 operations
  • Timing
    Available Types:
    On delay, Off delay, Pulsed interval, Maintained interval
    Repeat Accuracy:
    ± 1% of setting
    Reset Time:
    50 msec minimum
    Indication:
    Optional LED - ON when timing
    Timing Ramp:
    0.06 sec minimum time - 100k ohm/sec, .5 sec minimum time - 10K ohm/sec
    Time Range:
    0.06 to 500 secs in 12 ranges
    Range Tolerance:
    ≤ 10% at max., ≤ 0% at min.
    Control:
    Isolated contact closure
    Control Terminals:
    5/6/2014
    Voltage Present at Control Terminals:
    24 VDC minimum, 40 VDC maximum
  • Physical
    Operating Temp:
    0° to 50° C (32° to 120° F)
    Timing Variation vs. Temp:
    ± 5% maximum
    Mounting:
    Plug-in
    Termination:
    12 pin socket
    Housing:
    Metal

Wiring Terminal Location

1012 Timer Wiring

Dimensions

1012 Timer Dimensions

Ordering Data

1012 Timer Ordering