• Input
    Voltage:
    24V AC/DC, 48V AC/DC, 120VAC/125VDC, 240VAC/250VDC
    Frequency:
    50/60 Hz or DC
    Tolerance (voltage):
    ±15% of nominal, ± 10% for 24V
    Power Consumption:
    16 W Maximum
    Transient Protection:
    MOV
  • Output
    Type:
    Electromechanical relay
    Rating:
    3A @150 VDC Max, 10A @ 240 VAC 80% PF Max
  • Timing
    Available Types:
    On Delay
    Repeat Accuracy:
    ± 1% of setting
    Reset Time:
    50 msec minimum
    Time Range:
    1.5 to 120 cycles in 4 ranges or 0.5 to 300 sec in 4 ranges
    Range Tolerance:
    ≤ 10% at max., ≤ 0% at min.
  • Physical
    Operating Temp:
    40° to 65° C (40° to 150° F)
    Timing Variation vs. Temp:
    ± 5% maximum
    Mounting:
    Base Mount
    Termination:
    Terminal blocks on face of timer
    Housing:
    Metal

Wiring Terminal Location

Wiring

Dimensions

ISSC Kanson 1017 Timer

Ordering Data

Ordering