• Input
    Voltage:
    120VAC
    Frequency:
    50/60 Hz
    Tolerance (voltage):
    ± 10% of nominal
    Power Consumption:
    10 VA maximum
    Transient Protection:
    Isolation transformer
  • Output
    Type:
    Electromechanical relay or Solid State
    Rating:
    1.5A @ 120 VAC (solid state)10A @ 240VAC maximum (electromechanical)
  • Timing
    Available Types:
    Motion Detector
    Indication:
    LED indicates unit timing and output energized
    Timing Ramp:
    0.06 sec minimum time - 100kΩ//sec0.5 sec minimum time - 10kΩ//sec
    Time Range:
    0.06 to 500 secs in 12 ranges
    Range Tolerance:
    ≤ 10% at max., ≤ 0% at min.
    Control:
    Isolated contact closure or AC prox switch
    Control Terminals:
    P1-P2-L2
    Voltage Present at Control Terminals:
    P1-P2: Same as input voltageL2-P2: 120VAC pulse
  • Physical
    Operating Temp:
    -32° to 71° C (-25° to 160° F)
    Timing Variation vs. Temp:
    ± 3% maximum
    Mounting:
    Base Mount
    Termination:
    Terminal block on face of timer
    Housing:
    Metal

Wiring Terminal Location

1260 Timer Wiring

Dimensions

1260 Timer Dimensions

Ordering Data

1260 Timer Ordering